INCREASING OF REABILITY OF WORK OF BOILERS BY EQUAL DISTRIBUTION OF THE HEAT LOAD OVER THE HEIGHT OF FIREBOX

Authors

DOI:

https://doi.org/10.20535/1813-5420.4.2019.207092

Keywords:

heat perception, active combustion zone, posture calculation, screen tubes, wall temperature, service life

Abstract

Detection of one of the methods for reducing the emergency screens of boiler units pipes is in the process of being discovered. Specially used in the even distribution of heat load in the active combustion zone, replacing the burners with 1-2 tier arrangement by 2-4 tier, reducing the single power of the finger. Investigation of the supported solution, with the posture of the boiler. The mathematical calculation model and graphical division of the boiler furnace into combustion zones are presented. The results of the research showed that a large number of burners and a decrease in the unit power of the population, which reaches a greater uniform thermal voltage, are detected by the height of the shielded pipe, reducing peak maximum consumption from 100% to 86.5% (590 kW / m2 to 510 kW / m2) As the number of burners increases, the thermal load in the lower part of the combustion zone increases, which results in more intense boiling, as a consequence of the increase in the velocity of the vapor-liquid mixture in the screen tubes and, accordingly, the cooling of the evaporator tubes in the regions of the highest heat load. The temperature of the screen metal in the zones of maximum heat load of the pipes is reduced by 20-30 0C, which, with a long service life, leads to a decrease in temperature aging, and consequently an extension of the inter-repair life of the boiler. The disadvantage of this method is the complication and complication of the manufacture of screen pipes, increase the hydraulic resistance of the lifting pipes by increasing the number of bends of pipes, complicates the system of supply of fuel and air. The results of the calculations are presented in graphical form, as the dependence of the specific heat load, the temperature of the outer wall of the pipe, the allowable thermal stress, the height of the pipe at one-, two- and four-tier arrangement of burners in the zone of active combustion.

References

Meikler М.V. Modern boiler units TKZ 3 pub. / М.V. Meker. – Moscow, Energy, 1978. – 223 p.

Lokshin V.A. Hydraulic calculation of boiler units (normative method) / V.А. Lokshin, D.F. Peterson, А.L Schwartz. – Moscow, Energy, 1978. – 256 p.

Industrial Boilers and Heat Recovery Steam Generators Design, Applications, and Calculations By V. Ganapathy, ABCO Industries Abilene, Texas, U.S.A.2003

Holshchev VV, Comparative analysis of two experimental oil-fired boilers tested in different years / Power Plants, 2001, 3, p12-14

Weglowski, B, Taler, J, and Duda, P. Monitoring of thermal stresses in steam generators. Czech Republic: N. p., 2003. Web.

http://algoritmist.ru/korrozija-i-korrozionnye-povrezhdenija/xarakter-povrezhdenija-ehkrannyx-trub-gazomazutnyx-kotlov.html

Three-Dimensional Thermal Stress Distribution of Opposed Firing Boiler: Numerical Study and Experimental Verification Yunjin Ao; Na Li; and Qulan Zhou. 2019

Lebedev I.К. Hydrodynamics of steam boilers / I.К. Lebedev. – Moscow, Energyatompublisher, 1987. – 240 p.

Thermal calculation of boiler installations (regulatory method). 2 pub. / [N.V. Kuznetsov, V.V. Mitor, I.E. Dubovskiy and others]. – Moscow, Energy, 1973. – 296 p.

Standards for calculating the strength of stationary boilers and pipelines of steam and hot water GD 10-249-98 / [V.S. Kotelnikov, Y.K. Petrenia, N.А. Makhutov and others]. – Moscow, 1998. – 210 p.

Published

2020-03-05

Issue

Section

MONITORING, DIAGNOSTICS AND MANAGEMENT OF ENERGY PROCESSES AND EQUIPMENT